ELETTROTEK KABEL GAALFLEX® Tray 1002 CY Lean
Shielded flexible power tray cable
600V UL TC-ER, MTW, AWM 21179, 1000V Flexible Motor Supply, WTTC

Shielded construction:
Configuration: multi-conductor cable with one ground
Conductor: class 5 stranded bare copper, acc. to IEC 60228
Insulation: special PVC, GAALTHERM® 522
Color code: black w/ white #s, green/yellow ground
Shielding: aluminum tape and tinned copper braid
Jacket: PVC, black
ELETTROTEK KABEL’s line-up of flexible shielded tray cables includes the GAALFLEX® Control 1002 CY Lean. Offered from AWG 18 to 250 MCM and up to 25 conductors, GAALFLEX® Control 1002 CY Lean is rated 600V per UL TC-ER, MTW, AWM 21179 as well as 1000V UL 2277 Flexible Motor Supply Cable and WTTC making it a very versatile power and motor supply cable in a black PVC jacket. Also offered in a unshielded construction.
Voltage
600V UL TC-ER, MTW, AWM, 1000V Flexible Motor Supply, WTTC
Test Voltage
4000
Temperature
-40°C – +90°C static
Minimum Bending Radius
4 x cable OD
Conductor Marking
Black with white numbers and one green/yellow ground
*2C no ground included
Burning Behavior
(UL) FT4/IEEE, UL 1685
Oil Resistance
to UL OIL RES I
UV resistant / Sunlight resistant:
acc. to EN 50396 and HD 605 A1, UL 1581
-
AWM style 10012/21179 90°C 600 or 1000 V
-
c(UL) CONTROL CABLE CIC/TC PVC FT4,
-
CSA AWM I/II A/B 90°C 1000 V FT1
-
acc. to UL 1063 UL(MTW) “FLEXING” and UL 1277 (TC-ER) DIR BUR OIL RES I 600 V 90°C Dry / 75°C Wet FT4
-
acc. to UL 2277: Flexible Motor Supply Lead Cable and Wind Turbine Tray Cable (WTTC) 1000 V 90°C Dry
-
acc. to NFPA 79 2007 and NEC 336.10(7) class 1 Div. 2 art 336, 392, 501
-
Direct burial acc. to UL 1277 part. 5.2. (wet location insulations) and 18.1 – 18.6 (crushing test)
-
CE
-
RoHS
-
outdoor use
-
cable for tray use with exposed runs
-
oil resistance
-
water resistance
-
RoHS and CE approval